Arch International Est. 1996

HomeProductsSolenoid Coils and Valves

Brahma solenoid valve, model E6G SR

Solenoid Coils and Valves

Brahma solenoid valve

Model E6G SR Price on enquiry

Brahma E6G SR normally closed gas solenoid valve with quick opening, adjustable flow and quiet operation for civil and industrial gas burners.

Typically used in

  • Gas burners
  • forced-draught gas burners
  • atmospheric gas burners
  • heating boilers
  • steam boilers
  • hot-water boilers
  • industrial furnaces
  • industrial ovens
  • hot-air generators
  • radiant-tube heaters
  • commercial heating systems
  • process-heating equipment

Product overview

Details that help confirm the fit.

The Brahma E6G SR is a normally closed solenoid gas valve designed for automatic fuel control in civil and industrial gas-burner systems.

When electrical power is not applied, the valve remains closed and prevents gas from passing through the body. When the solenoid is energised, the valve opens rapidly and supplies gas to the burner. Removing electrical power closes the valve within one second.

The SR configuration combines quick opening with adjustable maximum gas flow. The flow-control mechanism allows the gas supply to be matched with the burner’s operating capacity during commissioning.

The E6G SR series is available with either an 8 mm or 10 mm internal orifice. The E6G SR8 supports operating pressures up to 1000 mbar, while the E6G SR10 supports pressures up to 500 mbar.

The valve is suitable for gases from the first, second and third gas families. Standard electrical versions operate from either 230 V AC or 110 V AC at 50/60 Hz.

The die-cast brass body provides a robust and compact construction suitable for burner gas trains. The valve can be installed in a vertical or horizontal position, with the flow-direction arrow aligned with the direction of gas movement.

Typical applications include forced-draught gas burners, heating boilers, steam boilers, hot-water boilers, furnaces, industrial ovens, hot-air generators, radiant-tube heaters and process-heating equipment.

The correct E6G SR8 or E6G SR10 configuration must be selected according to the required pipe connection, operating pressure, nominal flow rate and burner capacity. Installation, gas-flow adjustment, leak testing and burner commissioning must be performed by qualified personnel.

Model, voltage, rotation, pressure range and mounting can vary. Final compatibility is confirmed against the nameplate or existing component.

Specifications

E6G SR
Brand
Brahma
Series
E6G
Model
E6G SR
Product type
Solenoid gas valve
Valve operation
Normally closed
Opening type
Quick opening
Flow adjustment
Yes
Valve class
Class A
Valve group
Group 2
Gas compatibility
Gas families 1, 2 and 3
Nominal diameter
DN 8, DN 10 or DN 15
Maximum operating pressure
Up to 1000 mbar
Nominal gas flow rate
Up to 3.9 m³/h
Pipe connections
G 1/4 inch, G 3/8 inch or G 1/2 inch
Supply voltage
230 V AC
Supply frequency
50/60 Hz
Power consumption at 230 V
20 VA
Alternative supply voltage
110 V AC, 50/60 Hz
Power consumption at 110 V
18 VA
Operating temperature
-10 to +60°C
Closing time
Maximum 1 second
Opening time
Maximum 1 second
Valve body material
Die-cast brass
Mounting orientation
Vertical or horizontal
Applicable standard
EN 161
Compliance
EU Gas Appliances Regulation 2016/426

Price & availability

A clear quotation for this exact reference.

Tell us the quantity, application and delivery city. We will confirm fitment and availability before sending the quotation.

01

Reference checked against the product and application.

02

Availability confirmed before we commit a dispatch window.

03

Freight explained clearly in the quotation.

Ask for the price

We answer every enquiry, usually within a few hours. No customer account is required.

We call back on this number.

So we can quote freight.

Optional, for the quotation.

We answer every enquiry, usually within a few hours. Your number is used only to answer this enquiry.

Fitment support

The exact part starts with one clear reference.

Send the model number or a photograph of the burner rating plate. We will help identify the fitment, check availability and prepare a clear quotation.

Original vs duplicate Know the difference before you fit it WhatsApp us