Product overview

Details that help confirm the fit.

The SUNTEC AN 77 C is a positive-displacement gear pump designed for single-stage oil burners used in commercial and industrial heating applications. It incorporates a pressure-regulating valve with a hydraulic cut-off function and can be configured for either one-pipe or two-pipe fuel systems.

The AN 77 C designation identifies gear size 77, anticlockwise shaft rotation and a left-hand nozzle outlet when viewed from the shaft end. The direction of rotation and nozzle position must be matched with the burner motor, coupling and fuel-pipe arrangement before installation.

The pump is suitable for domestic heating oil, HVO, B100 biofuel and kerosene, subject to the complete model code and installation requirements. It can handle fuel with an operating viscosity from 2 to 75 cSt and a temperature from 0 to 60°C.

The internal gear set draws fuel from the tank through the built-in strainer and transfers it to the pressure-regulating valve. The valve maintains the selected nozzle pressure and provides a hydraulically operated cut-on and cut-off function according to pump speed, gear capacity and pressure setting.

During burner start-up, fuel initially returns through a special passage in the regulator piston. As pump speed increases, nozzle pressure rises rapidly and opens the regulator valve. When the burner motor stops and pump speed decreases, the valve closes as the gear-set capacity falls below the internal bypass flow.

In a two-pipe installation, excess fuel returns to the storage tank and pump bleeding is normally automatic. In a one-pipe installation, excess fuel circulates internally after the bypass plug has been removed from the return port and the return connection has been sealed correctly.

Although the AN pump incorporates a hydraulic cut-off valve, SUNTEC normally associates this series with an external in-line solenoid valve for controlled burner shut-off.

Typical applications include oil and diesel burners, heating boilers, steam boilers, furnaces, hot-air generators, thermic-fluid heaters, industrial ovens and process-heating equipment.

The complete pump reference must be checked before ordering because hub diameter, pump series, revision, pressure configuration and one-pipe or two-pipe setup can vary. Installation, fuel selection, pressure adjustment and commissioning must be performed by qualified personnel.

Model, voltage, rotation, pressure range and mounting can vary. Final compatibility is confirmed against the nameplate or existing component.

Specifications

AN77C
Brand
SUNTEC
Series
AN
Model
AN 77 C
Product type
Oil burner pump
Pump design
Positive-displacement gear pump
Burner operation
Single stage
Gear size
77
Shaft rotation
Anticlockwise, viewed from the shaft end
Nozzle outlet position
Left-hand, viewed from the shaft end
Valve function
Pressure regulation with hydraulic cut-off
Integrated solenoid valve
No
External in-line solenoid valve
Normally used
Piping configuration
One-pipe or two-pipe system
Fuel compatibility
Domestic heating oil, HVO, B100 biofuel and kerosene
Nozzle pressure range
10 to 20 bar
Standard factory pressure setting
14 bar
Operating viscosity
2 to 75 mm²/s (cSt)
Fuel temperature inside pump
0 to 60°C
Maximum inlet pressure
2 bar
Maximum return pressure
2 bar
Maximum suction vacuum
0.45 bar
Maximum rotational speed
3600 RPM
Inlet connection
G 1/4
Return connection
G 1/4
Nozzle outlet
G 1/8
Pressure gauge port
G 1/8
Vacuum gauge port
G 1/8
Strainer open area
20 cm²
Strainer opening size
150 µm
Shaft diameter
8 mm
Starting torque at 45 RPM
0.14 N·m
Mounting type
Flange or hub mounting
Mounting standard
EN 225
Connection thread standard
ISO 228/1
Bleeding in two-pipe operation
Automatic
Approximate weight
1 to 1.3 kg, depending on configuration

Price & availability

A clear quotation for this exact reference.

Tell us the quantity, application and delivery city. We will confirm fitment and availability before sending the quotation.

01

Reference checked against the product and application.

02

Availability confirmed before we commit a dispatch window.

03

Freight explained clearly in the quotation.

Ask for the price

We answer every enquiry, usually within a few hours. No customer account is required.

We call back on this number.

So we can quote freight.

Optional, for the quotation.

We answer every enquiry, usually within a few hours. Your number is used only to answer this enquiry.

Fitment support

The exact part starts with one clear reference.

Send the model number or a photograph of the burner rating plate. We will help identify the fitment, check availability and prepare a clear quotation.

Original vs duplicate Know the difference before you fit it WhatsApp us